What happens when Product isn't in the array? Read the loop again with that case in mind, and tell me what the IF at the bottom is for. Also, continuo...
Fitted a second 24VDC 5A supply for the PLC and the rack. Valves and HMI stay on the 10A. Commons tied at the ground bar. Jogged the manifold 20 times...
Two things stacked. T_Fast running up to 6.8ms in a 5ms period runs past the next trigger whenever a scan goes long, overlap, and it takes priority ev...
What are the drives running in, DC-Synchron or SM-Synchron? Each AX8000 has a DC tab in TwinCAT. A ramp that grows with the move and resets when it st...
Not the port. Overlap count going up means the 5ms trigger is arriving before the previous pass of T_Fast is done. What's the task's watchdog, what pr...
The coils say 24VDC 0.21A. So 8.4A if all 40 fire at once, plus the PLC and the rack and the HMI. That's over 10 isn't it.
One supply, 24VDC 10A, feeds the PLC, the rack, the valve manifold and the HMI. That's everything on it I think, panel builder's label. Meter can't ca...