RE: S7-1200 retain values survive a power cycle but go back to 0 after a download

Got there. Retentive on a 1200 means it survives power off and STOP to RUN and that is the whole of what it means, nothing to do with a battery becaus...

2 weeks ago
Reply
RE: S7-1200 retain values survive a power cycle but go back to 0 after a download

There's a tick box in the download dialog and mine said it would initialise the retentive memory. Untick that and the counter stays put. But the optio...

2 weeks ago
Reply
RE: S7-1200 retain values survive a power cycle but go back to 0 after a download

No card in the slot at all, it runs from internal memory. And if it was the backup would it not lose the counter overnight as well? Overnight is the b...

2 weeks ago
Reply
RE: Parts per minute goes to a huge number at power-up, divide by zero on an S7-1500

Working now. The cause was nothing to do with the controller, it was a Real divide by 0.0 handing the panel positive infinity, which is a real value s...

2 weeks ago
Reply
RE: Parts per minute goes to a huge number at power-up, divide by zero on an S7-1500

Put the compare in and the ### is gone. Bit odd now though. For the first few seconds the rate shows 0.0, which reads as if the line is stopped rathe...

2 weeks ago
Reply
RE: Parts per minute goes to a huge number at power-up, divide by zero on an S7-1500

Counter is a DInt, elapsed is a Real because it comes out of a CONV on a cyclic interrupt. So the DIV is Real by Real, I think, the block picked Real ...

2 weeks ago
Reply
RE: PNP prox on an ET 200SP F-DI safety input, short-circuit to P fault from the first scan

Supervisor ordered a magnetic safety switch with two channels, a 3SE6 I think. I wired it as petra66 listed, each channel on its own VS terminal, test...

3 weeks ago
Reply
RE: S7-300 goes to STOP with SF, diagnostics buffer says OB 121 not loaded

Changed the ANY length to 100 with type BYTE, and added OB121 that writes the block number and the address into DB99. Loaded it this morning, ran the ...

3 weeks ago
Reply
RE: PRONETA and TIA V17 find no PROFINET devices from the engineering VLAN, ping works

Right. So DCP is layer 2 and the office sits on a routed VLAN, which is why accessible devices and PRONETA couldn't see the line at all. Plugging into...

3 weeks ago
Reply
RE: PNP prox on an ET 200SP F-DI safety input, short-circuit to P fault from the first scan

What does OSSD mean? And my supervisor still wants to keep the prox because it's "more reliable than a switch with moving parts".

3 weeks ago
Reply
RE: S7-300 goes to STOP with SF, diagnostics buffer says OB 121 not loaded

The pointer. The counter picks the recipe number and I multiply it by the recipe size to get the byte offset in DB10. The length in the ANY I set to 1...

3 weeks ago
Reply
RE: S7-1500 ERROR LED on, diagnostics buffer area length error, CPU still in RUN

Sorry if this is basic, but would adding OB121 make it go away? I read that the programming error OB stops the error.

3 weeks ago
Reply
RE: PNP prox on an ET 200SP F-DI safety input, short-circuit to P fault from the first scan

3RG4012 something, I'll check tomorrow, a Siemens M18 PNP NO. Brown: panel 24V bus, the one the standard modules use. Blue: 0V bus. Black: DI3. I didn...

3 weeks ago