Took the laptop down to the line cabinet, plugged into a free port on the Scalance there, and PRONETA had all four IMs and the CPU listed straight awa...
Put FC105 in with 0.0 and 100.0 this morning. HMI shows 36.2 percent and it moves as the tank fills. So it was my own divide all along. Doing it in D...
Set the derivative time back to 0 and the twitch stopped at once. Then I moved the transmitter cable away from the pump cable and the PV noise went fr...
I couldn't find any way to exit the runtime, there's no button for it in my project. In the end I power cycled the panel and pressed Settings quickly ...
A Scalance in the main cabinet, and IT says the engineering VLAN is routed to the line VLAN on it. The PC's on a wall port in the office, a standard I...
Forced the heater first, the Pt100 climbed, so the loop was fine. Then I set RunModeByStartup to true, restarted the CPU, State went to 3 and Output s...
0 to 10 V, about 4 metres of cable, and its run along the pump cable. The PV trend at rest moves about 0.03 bar up and down every sample. I thought ma...
Sorry if this is basic, what's MRP? Same thing as a ring?
Yes, the old project's running, the start screen with my buttons on it. I've never opened the Transfer settings on the panel. My first download was do...
Mode isn't connected, ModeActivate isn't connected. I thought they were optional, maybe not. What does RunModeByStartup mean, is it the mode the block...