My wrong guess cost you a block. Decent spare now though.
Then stop looking at the network. That display only runs the catalogue number, the revision and the address at power up. If you are watching it start ...
C143, EN Comm Flt Actn. That's the parameter that decides it and it lives in the drive, not in your program. Default is Fault, which is what your oth...
Get the supplier to send another block. I reckon it's gone half alive on you, answers most of the time, and that beats a week of Wireshark.
Block 2 only, so look at block 2. Does its lead cross the saw anywhere?
Ring buffer beats a FOR loop in a fast task every time.
Touch it now. Zero errors means nobody has looked yet.
Meter reading in the file, not a drive trend.
What ron said. Every line-fed motor gets its own overload, no exceptions. For yours: electronic overload that clips under the contactor, class 10 trip...
Import the UDT, download at the next stop. Nothing else will fix that one.
Before anything: Task Properties, Monitor tab, what does Max Scan Time say for T_Weigh with the new routine in? And what's the max on the continuous t...
Errors move with the cable, not with the port and not with the card. That leaves the cable and whatever's next to it. What is the cable, and where doe...
Breaker is short circuit protection. It's sized for the starting inrush, 15 A on a 4.8 A motor is normal. A stalled 3 HP pulls maybe 30 A. On the brea...
Middle or end, you said middle. Did you change the L33ER's copy of the UDT too? And which addressing mode is the Kepware channel on, symbolic or logic...
Then T is not 300. Curtain, input, task, output, drive, mechanics, all of it, worst case. Measure it with a stop-time meter on the curtain, not with a...