Reply
2 weeks ago
Reply
RE: 1734-AENTR display keeps restarting and the Point I/O drop faults a few times a shift

Then stop looking at the network. That display only runs the catalogue number, the revision and the address at power up. If you are watching it start ...

2 weeks ago
Reply
RE: Filler PowerFlex 525 held its last command when the switch died, others faulted

C143, EN Comm Flt Actn. That's the parameter that decides it and it lives in the drive, not in your program. Default is Fault, which is what your oth...

3 weeks ago
Reply
RE: Modbus TCP gateway drops four seconds at a time since a remote I/O block was swapped

Get the supplier to send another block. I reckon it's gone half alive on you, answers most of the time, and that beats a week of Wireshark.

3 weeks ago
Reply
RE: Modbus TCP gateway drops four seconds at a time since a remote I/O block was swapped

Block 2 only, so look at block 2. Does its lead cross the saw anywhere?

3 weeks ago
Reply
RE: 1756-L73 major fault T06:C01 task watchdog expired after adding a routine

Ring buffer beats a FOR loop in a fast task every time.

3 weeks ago
Reply
3 weeks ago
Reply
RE: Line-fed screw conveyor motor burned out, panel builder skipped the overload

What ron said. Every line-fed motor gets its own overload, no exceptions. For yours: electronic overload that clips under the contactor, class 10 trip...

3 weeks ago
Reply
RE: Logix UDT member added, Kepware tags and the MSG on the other PLC read shifted values

Import the UDT, download at the next stop. Nothing else will fix that one.

3 weeks ago
Reply
RE: 1756-L73 major fault T06:C01 task watchdog expired after adding a routine

Before anything: Task Properties, Monitor tab, what does Max Scan Time say for T_Weigh with the new routine in? And what's the max on the continuous t...

3 weeks ago
Reply
RE: CRC errors on one Stratix 5700 port, patch lead runs through the PowerFlex 755 panel

Errors move with the cable, not with the port and not with the card. That leaves the cable and whatever's next to it. What is the cable, and where doe...

3 weeks ago
Reply
RE: Line-fed screw conveyor motor burned out, panel builder skipped the overload

Breaker is short circuit protection. It's sized for the starting inrush, 15 A on a 4.8 A motor is normal. A stalled 3 HP pulls maybe 30 A. On the brea...

3 weeks ago
Reply
RE: Logix UDT member added, Kepware tags and the MSG on the other PLC read shifted values

Middle or end, you said middle. Did you change the L33ER's copy of the UDT too? And which addressing mode is the Kepware channel on, symbolic or logic...

3 weeks ago
Reply
RE: Light curtain 200mm from the hazard, auditor wants the ISO 13855 distance for a 300ms stop

Then T is not 300. Curtain, input, task, output, drive, mechanics, all of it, worst case. Measure it with a stop-time meter on the curtain, not with a...

3 weeks ago