RE: Light curtain 200mm from the hazard, auditor wants the ISO 13855 distance for a 300ms stop
300 ms from what to what, exactly, and measured with what? A drive trend starts when the drive hears about it. The curtain heard about it earlier.
3 weeks ago
Forum
RE: 1791ES-IB16 safety connection times out a few times a day since a new managed switch
Faster RPI to fix a timeout. Everyone tries it once.
3 weeks ago
Forum
RE: 1791ES-IB16 safety connection times out a few times a day since a new managed switch
The RPI change tells you a lot. The connection reaction time limit on a safety connection is derived from the RPI times a multiplier. Halve the RPI, h...
1 month ago