It's over 10 before the inrush on 40 coils. The supply hits current limit and folds back, the rail drops under the controller's minimum for a few mill...
Green all the way through, that crimp was gone long before Tuesday.
Close enough. Two ways. In RSLinx, Communications, Configure Drivers, add an Ethernet devices driver instead of EtherNet removed link That one doesn'...
Check the chassis PSU LED anyway while you're in there. But it's the battery.
Not sure it's series yet. Ping the new EN2T from the primary side first, then worry about that.
What's the connection timeout on that rack. Not the RPI. The timeout.
That's the port sitting in listening and learning before it forwards. Set the ports facing a PLC or an HMI to portfast, on the Stratix the Automation ...
Nothing wrong with the module. Ping works, that's layer 3 and it goes through the router. RSWho with the EtherNet/IP driver finds modules by broadcast...
Solid red NET on an EN2T is duplicate IP detected. The module shuts its own port. It doesn't need a switch to do that. What address does the spare sc...
Don't swap it. Display scrolling BOOTP is the whole story, the module has no address. What are the three rotary switches on the front set to? Photo, t...
40 solenoids on a 10A supply. Do the sum.
The ring did exactly what it's for. First break, it heals, nothing stops. Second break, two islands. Nobody looked at the supervisor status for six we...
Not a virus. A cable from a switch back to itself is a loop, and the switch is supposed to block that on its own. Is spanning tree turned on?
Hannah has it. Chassis Size on a 1734 is modules plus the adapter itself, so 9 for you, and 8 was right when you had 7 modules. Set it to 9 in Module ...
No firmware. Open the AENT in the tree, Module Properties, General tab. What does Chassis Size say?