RE: CIP Generic MSG to a PowerFlex 525 comes back 16#0005 every time

Everything in that dialog is hex. Learned that one the same way.

2 weeks ago
Reply
RE: CompactLogix 1769 bank, slot 4 faults 16#0114 after a download, rest of the rack fine

There it is. Stop pulling hardware and go read the label. 16#0114 is the controller saying the product code of the card in the slot isn't the product...

3 weeks ago
Reply
RE: 1756-OB16E output tag is 1 but the solenoid has no voltage

We alarmed the I.Fuse bits on every OB16E after the same thing on a filler. Cheap.

3 weeks ago
Reply
RE: Eleven remote racks drop 16#0204 at line start-up, 1756-EN2T fine once running

The drives were winning the argument. Every contractor leaves 2 ms in, I've seen it a dozen times.

3 weeks ago
Reply
RE: CompactLogix faults T03:C16 every time the remote Point I/O rack loses power

Same box bit us on a filler in 2019. Still don't know who ticked ours.

3 weeks ago
Reply
3 weeks ago
Reply
RE: 1756-EN2T faulted, 16#0204 connection request error after weekend power outage

Pat has it. Laptop on the same switch, open the BOOTP-DHCP EDS tool, the module's MAC shows in the request list within a minute. Add relation 192.168....

3 weeks ago
Reply
RE: 1734-AENTR over industrial wifi drops 16#0204 a few times an hour

Two things, both in the AENTR's module properties. Raise the RPI to what the process actually needs, a clarifier bridge doesn't need 20 ms, 100 ms is ...

3 weeks ago
Reply
RE: Eleven remote racks drop 16#0204 at line start-up, 1756-EN2T fine once running

23000 is right under what an EN2T can do. What RPI on the racks?

3 weeks ago
Reply
Reply
RE: 1756-EN2T solid red NET LED after a spare went in, duplicate IP on another line

The spare's fine. I reckon it kept 192.168.10.41 from the line 2 palletizer, somebody pulled it on a repair and put it back in the crib without cleari...

3 weeks ago
Reply
RE: MSG error 16#0005 path destination unknown to a second ControlLogix

Doesn't have to be anything. Last two numbers of your path, read them again.

3 weeks ago
Reply
RE: 1756-EN2T racks fault 16#0203 hourly, HMI PC freezes ten seconds at a time

Unmanaged switch and four racks of I removed link Before you blame the PC, open Task Manager on it, Performance, Ethernet, and read the receive rate ...

3 weeks ago
Reply
RE: CompactLogix reboots whenever a bank of solenoids fires

It's over 10 before the inrush on 40 coils. The supply hits current limit and folds back, the rail drops under the controller's minimum for a few mill...

3 weeks ago