Reply
RE: S7-1200 slot 3 SM 1223 faults after a download, rest of the rack runs

So what is TIA actually comparing when it loads, the program or the hardware?

3 weeks ago
Reply
RE: KTP700 Basic shows

Fixed. First I unticked optimized to watch the values come back, and they did. Then I turned it back on and re-linked the eight HMI tags to the DB1 sy...

3 weeks ago
Reply
RE: ET 200SP F-DQ 4x24VDC PM read-back error the moment it switches a contactor coil

Ran it all morning, output on and off two hundred times off a test bit, no passivation, contactor follows every time. The module was right and my wir...

3 weeks ago
Reply
RE: S7-1200 HSC misses pulses from a 2 kHz encoder, counts about half

Set the input filter on channels 0 and 1 to 12.8 us, downloaded, and the count is 400 per turn at full speed now, checked over a minute against the sc...

3 weeks ago
Reply
RE: SM 1231 current input reads 0 with a 2-wire 4-20mA level transmitter

Rewired it as a loop through the 24V supply, meter reads 12.1 mA at half tank, raw value about 16700, same as the old one gave. So the 2-wire transmi...

3 weeks ago
Reply
RE: ET 200SP F-DQ 4x24VDC PM read-back error the moment it switches a contactor coil

Moved A2 to the M for channel 0 and the output holds, contactor stays in. Sorry if this is basic, but why does the module care? I get that it switches...

3 weeks ago
Reply
RE: SINAMICS G120 F01910 fieldbus setpoint timeout when the PLC goes to STOP

Understood now. Nothing to fix on the drive, the p2040 monitoring time runs out because the CPU stops sending a valid setpoint, and the drive is suppo...

3 weeks ago
Reply
RE: PROFIBUS DP at 1.5 Mbit/s over a 300 m segment, far slaves drop with BF flashing

This is new to me, and I'm not sure I follow. Why does the allowed length go down when the speed goes up? Is it the cable getting worse, or the signal...

3 weeks ago
Reply
RE: TIA V16 PLCSIM load fails, "simulation is not supported" for a block

Ticked "Support simulation during block compilation" in the project properties, rebuilt all, loaded to PLCSIM, and the conveyor runs in the sim now. ...

3 weeks ago
Reply
RE: KTP700 Basic shows

Yes. The old ones say things like "%DB1.DBW0" and "%DB1.DBX2.0" in the PLC tag column. The new one I dragged in says "Tank".Level. Screenshot attached...

3 weeks ago
Reply
RE: S7-1200 HSC misses pulses from a 2 kHz encoder, counts about half

Push-pull, 24V output, measured right at I0.0 and I0.1 on the CPU terminals. 250 us high, 250 us low, clean edges. Screenshots of both channels attach...

3 weeks ago
Reply
RE: ET 200SP F-DQ 4x24VDC PM read-back error the moment it switches a contactor coil

6ES7136-6DB00-0CA0. Wires: A1 to terminal 1 on the F-DQ, which the label says is DQ0 P. A2 to the 0V bus on the bench, the same bus the CPU and the 24...

3 weeks ago
Reply
RE: SINAMICS G120 on S7-1500 telegram 1, r0052 ready to switch on but never runs

Is the speed setpoint scaled right? On my bench drive 16#4000 is 100 percent, so 16#2000 is only half, and I once had a minimum speed set that made it...

3 weeks ago
Reply
RE: KTP700 Basic shows

Connection's established, green in the diagnostics view. Panel image is V17, same as the project. Sorry if this is basic, two evenings on it now and n...

3 weeks ago