Which page of the manual, and does it give the two registers as high word first or low word first? Some meters print it in the notes as "float, LSW fi...
Middle, after Speed_Act. Didn't touch the L33ER, I didn't think a MSG cared about the layout. Kepware channel is logical blocking, or I think it is, w...
Ordered one, be here Thursday. Adding up from the SG001 I get about 1.05A for all 20, which is right at the edge, and the OB8s at the end are where it...
Deadband on the analog ones as well, or the 20 keepers will chatter.
Which of the 1200 are on the P&ID as required alarms, and which got added because the tag existed and the range was there? A low flow alarm on a f...
Then the drive's on your cable, not on your meter. Fix that first, filter second.
20 exactly. No EP24DC, never heard of it. Firmware on the AENTR is 5 something. Order is 8 IB8, 4 OB8, 2 OE2V, then 6 more OB8 on the end. The OB8s at...
Tag and range first. Channel 0 is scaled 0 to what, and what does the meter itself show on its display while the PLC shows 410 then 398? Is the bounce...