RE: Ignition historian grew 40 GB in a month from 300 tags, every analog logs every scan

Numbers we run, for what they're worth. Deadband off the alarm band rather than the range: about a tenth of the gap between normal and the alarm limit...

3 weeks ago
Reply
RE: PanelView Plus 7 on the cartoner went slow the day Ignition was connected to the L33ER

How many tags did the integrator subscribe, and in what tag group?

3 weeks ago
Reply
RE: Ignition 8.1 Logix driver faulted on a 1756-EN2T, CIP connection request error 16#0100

EN2T's on 10.something, I'd have to check. Device poll is default. The Kepware box has one channel to that PLC that I know of. Historian is subscribe...

3 weeks ago
Reply
RE: ET 200SP inputs on the last two modules drop to 0 whenever the guard door opens

Traced it. L+ on base 11 comes from terminal strip X4, and X4 is fed from the output side of the safety contactor K2, the one the door drops out. The ...