RE: PanelView Plus 7 on the cartoner went slow the day Ignition was connected to the L33ER

Let IT swap the switch. Costs nothing, keeps them off the gateway.

3 weeks ago
Reply
3 weeks ago
Reply
RE: Ignition MQTT Engine shows no tags, broker sees every message from the gateway

The broker log telling you what it subscribed to. Nice catch.

3 weeks ago
Reply
RE: Ignition to KEPServerEX OPC UA, BadCertificateHostNameInvalid from the server room only

Suffix was blank. Set it, rebooted, reissued, and the SAN now has kep01 and kep01.plant.local on it. Deleted the old cert in the gateway, reconnected,...

3 weeks ago
Reply
RE: PowerFlex 525 F005 overvoltage every time the fan stops

Tried 15 first. Still faulted once out of five stops. Went to 25 and it stopped clean all afternoon, bus climbed to just over 700 on the display and c...

3 weeks ago
Reply
RE: Ignition Edge MQTT Transmission, ten minute gaps in cloud data after every WAN drop

Cloud side is stamping on arrival. Make it read the timestamp in the payload.

3 weeks ago
Reply
RE: Studio 5000 refuses online edit, pending edits exist in another routine

Opened R_Glue, three rungs with I and R marks, a purge timer change and a new interlock on the glue pot heater. That's been running since March and no...

3 weeks ago
Reply
RE: Ignition can't reach a 1756-L72 on VLAN 20 from VLAN 10, IT says routing is fine

.254 timed out from the VLAN 20 laptop too. IT went and looked properly, and the SVI on VLAN 20 is 10.20.1.1, the .254 thing is just their template fo...

3 weeks ago
Reply
RE: Ignition to KEPServerEX OPC UA, BadCertificateHostNameInvalid from the server room only

Reissued it, restarted the runtime. The new cert SAN is still DNS kep01 and 10.20.5.14, no FQDN in it at all, and the gateway still faults. Three days...

3 weeks ago
Reply
RE: ET 200SP inputs on the last two modules drop to 0 whenever the guard door opens

Moved the X4 feed over to X2 this morning, so both groups sit on the unswitched 24 VDC now. Door open, inputs stay on. So the new light base started ...

3 weeks ago
Reply
RE: PowerFlex 525 F005 overvoltage every time the fan stops

P042 says 3.0. When we put this drive in last year we copied the parameters off the conveyor drive next to it, same size frame I think. Direct wheel ...

3 weeks ago
Reply
RE: Ignition to KEPServerEX OPC UA, BadCertificateHostNameInvalid from the server room only

SAN says DNS kep01, IP 10.20.5.14. Nothing with plant.local in it anywhere. So the gateway asks for kep01.plant.local and the cert doesn't claim that...

3 weeks ago
Reply
RE: PanelView Plus 7 on the cartoner went slow the day Ignition was connected to the L33ER

Add to that: set the screen-only tags to leased so they only poll fast while a client has them open.

3 weeks ago
Reply
RE: Ignition Edge MQTT Transmission, ten minute gaps in cloud data after every WAN drop

900 tags at what rate? And is the Edge historian actually storing through the outage, or just holding the last value for each tag?

3 weeks ago
Reply
RE: Studio 5000 refuses online edit, pending edits exist in another routine

R_Glue has the marker, I never even opened it. 31.011 yes. A contractor was in for the glue system back in March, so 6 months.

3 weeks ago