RE: STEP 7 V5.5 says object not found with 256:31 and I cannot find that number anywhere

You can't find it because you're searching the wrong family. A code with 256 in front of the colon is a SIMATIC Manager message number, not a CPU even...

2 weeks ago
Reply
RE: S7-1200 slot 3 SM 1223 faults after a download, rest of the rack runs

Both, and they are separate loads. The hardware configuration is a description of what should sit in each position, order number included. At every st...

3 weeks ago
Reply
RE: New FactoryTalk View ME app runs on the laptop, no live values on the PanelView Plus

That was it exactly. Runtime (Target) tab was empty, FILLER1 only existed on the Design side, and the terminal was looking for a controller that was n...

3 weeks ago
Reply
RE: New FactoryTalk View ME app runs on the laptop, no live values on the PanelView Plus

Went through all of them, the numerics are all Analog and the tags are all DINT or REAL in the controller. No stray spaces, I checked in the tag brows...

3 weeks ago
Reply
RE: New FactoryTalk View ME app runs on the laptop, no live values on the PanelView Plus

Diagnostics list is full of the same line over and over, something about not being able to resolve an item and then the shortcut name, FILLER1. It rep...

3 weeks ago
Reply
RE: KEPServerEX 6 S7-1500 items on DB5 return address out of range, DB1 reads fine

Six more is the argument for the OPC UA route. Next stop, not this one.

3 weeks ago
Reply
RE: PLCSIM Advanced instance running, TIA Go online shows no accessible devices

Search is DCP, it finds by name before IP. The download needs the subnet.

3 weeks ago
Reply
RE: S7-1500 OPC UA connection refused from the office subnet, works from the plant

OPC UA is its own port, 4840 by default, and a rule for S7 on 102 says nothing about it. Ask IT for one rule, TCP 4840 from 10.10.2.40 to 10.20.7.5, t...

3 weeks ago
Reply
RE: S7-1500F F-DI channel stays at substitute value 0 after the fault is gone

ACK_REQ to a lamp, then nobody guesses which door wants a press.

3 weeks ago
Reply
RE: Single channel E-stop through one relay on a 1998 bagger, what PL does that reach

I would not assume the integral aux on a standard contactor is a mirror contact. If it is, the label carries the symbol, so look before you count on i...

3 weeks ago
Reply
RE: Publish MQTT straight from the S7-1500 with LMQTT, or put an edge gateway in?

One point I'd argue. I think LMQTT in the CPU is fine on a small standalone machine with nobody behind it and one broker on the same LAN, we've got on...

3 weeks ago
Reply
RE: KEPServerEX 6 S7-1500 items on DB5 return address out of range, DB1 reads fine

It matters completely. DB5 has optimized block access. An optimized DB has no absolute addresses, the CPU places the variables itself, so DB5,W0 does ...

3 weeks ago
Reply
RE: S7-1500 OPC UA connection refused from the office subnet, works from the plant

The certificate can't refuse a TCP connection. Certificates are checked after the socket is open, during the OPC UA handshake, and a rejection there r...

3 weeks ago
Reply
RE: Single channel E-stop through one relay on a 1998 bagger, what PL does that reach

One question first: was the PLr d from a fresh risk assessment of this machine, or copied from a template? It changes what you build. Assuming it sta...