RE: Conveyor PowerFlex 525 won't restart after an e-stop until the run bit is toggled

Added the AND. E-stop, reset, conveyor restarts on its own. Second shift ran it through a dozen e-stops, fine every time. The run bit that never drop...

32 minutes ago
Reply
RE: TLS3-GD2 guard lock releases a second after Stop while the spindle is still coasting

What does the risk assessment say about access while the spindle is rotating? That decides whether a validated time delay is acceptable at all, or whe...

5 hours ago
Reply
RE: 1769-L33ER major fault T04:C20 array subscript too large, once a shift

Controller's fine. Recipe[20] means elements 0 to 19. What is Idx when it faults? The fault log won't tell you but the HMI will: what does the operato...

9 hours ago
Reply
RE: 12 zone accumulation conveyor in a CompactLogix, twelve copies of the same zone rungs

Figured zone 12 would be the odd one. 100ms over a MSG sounds right.

11 hours ago
Reply
RE: Consumed tag error 16#0127 invalid connection size after editing a UDT

Did you download the new UDT to the downstream controller too, or only upstream? Both on 32.011 or whatever you're on?

14 hours ago
Reply
RE: 12 zone accumulation conveyor in a CompactLogix, twelve copies of the same zone rungs

One AOI for the zone, an array of zone UDTs, called twelve times. The rule "run if the next zone is clear" lives in the AOI once and the delay lives i...

23 hours ago
Reply
RE: Conveyor PowerFlex 525 won't restart after an e-stop until the run bit is toggled

F059 on the e-stop, reset clears it. Looked at the logic on the three good ones, their run bit is ANDed with the safety OK bit so it drops on the e-st...

1 day ago