Forum

larsdk
@larsdk
New Member
Joined: Dec 15, 2024
Last seen: Sep 19, 2026
Topics: 1 / Replies: 12
Reply
RE: SISTEMA gives PL c for a Cat 3 door interlock on an S7-1500F, needed PL d

Good. Now wire it and put FDBACK in, otherwise the SISTEMA file describes a machine that doesn't exist. Longer version of the category and PL side her...

3 weeks ago
Reply
RE: ET 200SP F-DI 8x24VDC HF passivates a guard door switch with a discrepancy error

For something else, and not for a door like that. And nobody drop that pair to single channel to dodge the fault, the diagnostics are the safety engin...

3 weeks ago
Reply
RE: ET 200SP F-DQ 4x24VDC PM read-back error the moment it switches a contactor coil

Because the M side is a safety channel, not a return. If A2 sits on the bench 0V and someone shorts A1 to 24VDC, the coil stays pulled in and nothing ...

3 weeks ago
Reply
RE: PID_Compact drives the chiller valve wide open when the tank gets cold, S7-1200

Open the PID_Compact configuration, Basic settings, and tick InvertControl. The boiler loop wants more output when the PV is below setpoint, a chiller...

3 weeks ago
Reply
RE: S7-1500F F-DI channel stays at substitute value 0 after the fault is gone

Not without the safety engineer. ACK_NEC TRUE means after a passivation the channel does not come back by itself, it waits for a rising edge on ACK_RE...

3 weeks ago
Reply
RE: SISTEMA gives PL c for a Cat 3 door interlock on an S7-1500F, needed PL d

Exactly. The fix is EDM, feedback from the contactors. The NC auxiliary blocks for a 3RT2 come as mirror contacts, check the type on the ones actually...

3 weeks ago
Reply
RE: ET 200SP F-DQ 4x24VDC PM read-back error the moment it switches a contactor coil

There's your fault, and it isn't the coil. That module is PM switching. It switches the P side and the M side of the load, and it reads both back. You...

3 weeks ago
Reply
RE: S7-1500F F-DI channel stays at substitute value 0 after the fault is gone

Both your 24VDC F-DI modules are fine then, still on TIA V17. ACK_REQ TRUE means the channel's repaired and waiting to be let back in. What writes ACK...

3 weeks ago
Reply
RE: ET 200SP F-DI 8x24VDC HF passivates a guard door switch with a discrepancy error

What's the discrepancy time in the channel parameters for that pair, and what exactly is the switch, part number? I'm not guessing at a time without k...

3 weeks ago
Reply
RE: Two hundred low flow and low pressure alarms on every plant startup, operators ack blind

Pump alarms are done. Running bit AND the 30000ms TON in the In condition of each ALMD, filters next week at three minutes. This morning's restart aft...

3 weeks ago
Reply
RE: SISTEMA gives PL c for a Cat 3 door interlock on an S7-1500F, needed PL d

What DC did you enter for the output subsystem, and how are the contactors monitored? Is there a feedback loop from the contactors back into an F-DI, ...

3 weeks ago
Reply
RE: Two hundred low flow and low pressure alarms on every plant startup, operators ack blind

Honestly, maybe 20. The rest are "that pump isn't running" in different words. The radio link to the north tank drops a couple of times a week as well...

3 weeks ago