There's your fault, and it isn't the coil. That module is PM switching. It switches the P side and the M side of the load, and it reads both back. You...
Both your 24VDC F-DI modules are fine then, still on TIA V17. ACK_REQ TRUE means the channel's repaired and waiting to be let back in. What writes ACK...
What's the discrepancy time in the channel parameters for that pair, and what exactly is the switch, part number? I'm not guessing at a time without k...
Pump alarms are done. Running bit AND the 30000ms TON in the In condition of each ALMD, filters next week at three minutes. This morning's restart aft...
What DC did you enter for the output subsystem, and how are the contactors monitored? Is there a feedback loop from the contactors back into an F-DI, ...
Honestly, maybe 20. The rest are "that pump isn't running" in different words. The radio link to the north tank drops a couple of times a week as well...