Reply
RE: Logix PID loop swings with a 40 second period after moving it out of a periodic task

Was the valve proved before you blamed the software? Stroke it 0 to 100 from the HMI in manual and watch the position feedback follow. A positioner wi...

3 weeks ago
Reply
RE: MicroLogix 1400 CTU counts two or three per bag from a photoeye, count 15 percent high

Both, then. Tilt the eye as carl says and keep the timer, because any eye will give you a short edge sooner or later. Final rung: I:0/3 into a TON, T...

3 weeks ago
Reply
RE: 4-20 mA level signal noisy since a PowerFlex 755 went in

A soft starter does not switch at 4 kHz. Pull the filter.

3 weeks ago
Reply
RE: 1769-IQ16 input chatters after wiring it in parallel with a 1734-IB8S safety input

Yes. Put a scope on that wire, or a fast meter, and you'll see 24V with a short drop every so often. That's the IB8S pulling T0 low for a moment and c...

3 weeks ago
Reply
RE: PID_Compact stays Inactive on an S7-1200, State 0, Output never moves

Before the software, one check: with the heater forced on from a watch table, does the Pt100 climb? If yes the loop is proved and it is only the block...

3 weeks ago
Reply
RE: PID_Compact output twitches between 40 and 60 percent as soon as I add derivative

Trend the PV on its own for a minute at 100 ms, nothing else changing. How much does it move when the process is sitting still? And the transmitter, 4...

3 weeks ago
Reply
RE: Modbus RTU RS-485 to six meters on a MicroLogix 1400, timeouts on the far three

400 ft is nothing for RS485, a kilometre works at 19200. Before you buy a repeater: with the master idle, what DC voltage do you read A to B at meter ...

3 weeks ago
Reply
RE: MicroLogix 1400 CTU counts two or three per bag from a photoeye, count 15 percent high

No. A CTU counts the rising edge of its rung, one per false to true, however many scans the rung then stays true. So the eye's giving you more than on...

3 weeks ago
Reply
RE: MB_CLIENT on S7-1200 reads the wrong registers from a power meter, values shifted

Before the block, prove the meter. With a laptop Modbus tool, read holding register 3000 and see what comes back. If the tool shows 231 V at 3000 and ...

3 weeks ago
Reply
RE: 4-20 mA level signal noisy since a PowerFlex 755 went in

Both ends grounded turns the shield into a conductor between two grounds that are not at the same potential when a 755 is switching. Current flows on ...

3 weeks ago
Reply
RE: 2-wire prox keeps an S7-1200 input on with nothing in front of it

A 2 wire sensor has no separate supply. It powers itself through the load, your input, so even when off it passes a small current to keep its electron...

3 weeks ago
Reply
RE: S7-300 SM 331 level scaling shows only 0, 25, 50, 75 percent, DINT maths

Before the maths, prove the loop. Put a meter in series with the transmitter. What mA at the level you've got right now, and at the same moment what d...

3 weeks ago