RE: MicroLogix 1400 CTU counts two or three per bag from a photoeye, count 15 percent high

Ran both for 300 bags. Raw counter 351, the one behind the 30ms timer 302, hand tally 300. So the timed one is near enough right and the raw one's way...

3 weeks ago